what is local code? does your civil parish have a website?
its only 4 if you use C class breaker and that is mounted on a din rail. That is another reason I like the elg drivers better you can have 6 on a class c breaker 4 on a b class@CobKits, do you know if thats a conservative number(as its meanwell)
Also, why it's only 4? seems like we have loads of amperage at the socket going unused...
That says the inrush current is 75a? No circuit could handle 75a.
If you have a 16a breaker which can handle 3600w and you have say 300w drivers.
Your circuit breaker will trip every time you turn more than a couple of drivers on at once?
If you turn on one at a time if it spikes the first time at 3000w not too bad it goes down to 300w out of 3600
You turn 2nd one on it spikes at 3000w plus the original 3300w still ok
Now your at 600w you turn next one on and another spike of 3000w is 3600w
Then it goes down to 900w next time you turn a driver on... spike 3900w trips breaker?
So you can only run 900w from a 16a breaker?
This is news to me I need to use 27 drivers... i can't have that many plugs. That would mean I'd need just as many timers as I do plugs that would be insane.
What's the reason why we can't have so many drivers on the same plug?