Laughinggrass420
Active Member
Finally bought a home & finally have the ability to grow with no partners or boss.
Room dimension
18 feet x 15 feet x 9 feet
12 800 watt leds
108 plants ( 9 per light or 4x4)
2 gal coco containers on irrigation.
figuring on avg +- 2000 milliliters/day per plant.
2000x108 plants =216,000 Milliliters/day.
216,000/3800=56.8 gallons
56.8x8 ( pints) =454.7pints/day
This is how I came up with my Dehu needs. Little under spec with dehus just slightly but thinking the a/c will help with the small gap.
total watts in the room :
Lighting 800x12= 9,600 watts
2 Anden 210 pint dehums =3,200 watts
Wall fans and misc = 1,500 watts
total watts 14,300.00
X4 btu. = 57,200.00 btu’s of cooling needed or 4.75 tons.
for some reason almost 5 tons of cooking seems in my mind, a little bit over kill for a 12 lighter in this size room.
also should note I’m in the northeast. Hot humid summers & cold dry winters.
my numbers making sense?
if they are there lies the question what to do about hvac?
do I go mini splits? Do I bite the bullet and get a 5 ton air handler? Friends of mine have mentioned reheat but I don’t fully understand it.
if I do go the mini split route I’ve been seeing units that you can duct in as opposed to just having the heads which I gotta say intrigues me for cooling distribution.
anyways point out my weak spots people! Any insight is appreciated as I wanna build this room out correctly from the start
If I missed any details that are vital let me
Room dimension
18 feet x 15 feet x 9 feet
12 800 watt leds
108 plants ( 9 per light or 4x4)
2 gal coco containers on irrigation.
figuring on avg +- 2000 milliliters/day per plant.
2000x108 plants =216,000 Milliliters/day.
216,000/3800=56.8 gallons
56.8x8 ( pints) =454.7pints/day
This is how I came up with my Dehu needs. Little under spec with dehus just slightly but thinking the a/c will help with the small gap.
total watts in the room :
Lighting 800x12= 9,600 watts
2 Anden 210 pint dehums =3,200 watts
Wall fans and misc = 1,500 watts
total watts 14,300.00
X4 btu. = 57,200.00 btu’s of cooling needed or 4.75 tons.
for some reason almost 5 tons of cooking seems in my mind, a little bit over kill for a 12 lighter in this size room.
also should note I’m in the northeast. Hot humid summers & cold dry winters.
my numbers making sense?
if they are there lies the question what to do about hvac?
do I go mini splits? Do I bite the bullet and get a 5 ton air handler? Friends of mine have mentioned reheat but I don’t fully understand it.
if I do go the mini split route I’ve been seeing units that you can duct in as opposed to just having the heads which I gotta say intrigues me for cooling distribution.
anyways point out my weak spots people! Any insight is appreciated as I wanna build this room out correctly from the start
If I missed any details that are vital let me