So I am looking to set up a small grow,
I want to use a 4x8 tent with 2 1000watt hps with cool tubes.
I had some questions I need help with..

1. Can I run 2 1000watt hps on 1 breaker?
2. will I need an AC unit?
3. Can I bring in cold air from outside, instead of using an a/c unit? (winter time in the north east, VERY cold) Or is the temperature to unpredictable?


My goal is to produce 3lb every 2 month, I have 2, 3x3 tents for veg, I will only be using the big tent for flowering.
 

Tupapa

Well-Known Member
So I am looking to set up a small grow,
I want to use a 4x8 tent with 2 1000watt hps with cool tubes.
I had some questions I need help with..

1. Can I run 2 1000watt hps on 1 breaker?
2. will I need an AC unit?
3. Can I bring in cold air from outside, instead of using an a/c unit? (winter time in the north east, VERY cold) Or is the temperature to unpredictable?


My goal is to produce 3lb every 2 month, I have 2, 3x3 tents for veg, I will only be using the big tent for flowering.
Do u have any successful grows under your belt already? If not try to start small, get ur feet wet first and then think big. GL
 

ruwtz

Well-Known Member
1. What size breaker? And what else is on the circuit?

2. You could vent from outside with a fan on thermostatic controlled outlet instead of AC. Can't speak for its reliability but certainly more cost effective to run than AC
 

thumper60

Well-Known Member
So I am looking to set up a small grow,
I want to use a 4x8 tent with 2 1000watt hps with cool tubes.
I had some questions I need help with..

1. Can I run 2 1000watt hps on 1 breaker?
2. will I need an AC unit?
3. Can I bring in cold air from outside, instead of using an a/c unit? (winter time in the north east, VERY cold) Or is the temperature to unpredictable?


My goal is to produce 3lb every 2 month, I have 2, 3x3 tents for veg, I will only be using the big tent for flowering.
please don't run 2 1k bulbs on a 20 amp fuse
 

WeedFreak78

Well-Known Member
15A or 20A breaker? No circuit should be loaded past 80% of its rated capacity to allow a cushion for start up draw/etc. So no more than 16A of equipment on a 20A circuit. 1000W lights run around 9A ea, or 18A for 2. That will be pushing the capacity of a 20A circuit. If you staggered the startup of your lights by a min or two, you could probably get away with it, but NOTHING else should go on that circuit.

If its a 15A breaker, you can run 1 1000W, plus have about 4A of capacity for a fan, pump, etc.
 