currently i have 6 qb96 on a frame with an hlg-600h-54b remotely wired, so the circuit is like 54v 11.8A
the driver has about a 6' run to the frame, for which i used 14/2 cable (because its what i had). and when i ran a ground wire separately i only had 18awg solid wire. now i'm thinking the 18awg ground wire wouldn't even be able to handle the current of a short and its really just useless and i need a bigger ground wire? also, does the resistance of the 6' run of 18awg matter if its being used as a ground?
if i am going to upgrade the ground wire would 16awg be enough or should i just do 14awg?
the driver has about a 6' run to the frame, for which i used 14/2 cable (because its what i had). and when i ran a ground wire separately i only had 18awg solid wire. now i'm thinking the 18awg ground wire wouldn't even be able to handle the current of a short and its really just useless and i need a bigger ground wire? also, does the resistance of the 6' run of 18awg matter if its being used as a ground?
if i am going to upgrade the ground wire would 16awg be enough or should i just do 14awg?