Well-Known Member
Sorry about that missed a whole page of reading. Great thread! +rep
Sure, you can plug an HID into a GFI. A GFI is just that, it protects against ground faults, not voltage spikes. You may be think if AFCI which will trip the breaker when a very small arc occurs.Can you plug a HID Ballast into a GFCI protected circuit, one that trips between 4-6mA not the GFI type that trips at 30mA. Because the winding in the ballast will take a few mS to return on the current carrying neutral thus leaving in imbalance in the startup only which would trip the GFCI. I ask because I was going to run my shit on an ungrounded floating delta system so I can have one ground fault without tripping the system. The Ground fault protection will be around the B phase. Also I know I can cornerground the B phase, but not really feeling like taking a power outage. An ungrounded system definately needs ground fault protection but I don't want nuessance tripping! ARGGGGG
bricktown- thanks for your input on this. it arrived the other day and i lucked out. it was indeed a "pulse start" ignitor with no separate capacitor needed. AND.. both components had wiring diagrams labled on the side. i connected everything just to test it and it worked like a champ. i have since mounted the transformer and ignitor in a cpu power supply box, used the existing terminal to wire the grounded power cord and used an 8 foot 14 gauge lamp cord for the mogul socket. turned out to be a nice little DIY remote ballast for under 25.00. i'll post pics of it if that's ok with you...hey man, great thread. lots of good info here. how would you wire this hps ballast / ignitor /socket? It is a 120v 100 watt HPS. I have a 120v heavy duty grounded power cord to use for this.
just need to know what wire goes where...
How would I connect a computer fan to a 110v outlet? Thanks
Installing a circuit breaker is a matter of turning a flat head screw driver a couple times. But you can't put a larger circuit breaker into replace a smaller one becuase the wire size is only suited for that breaker size. If you want to upgrade your breaker size you will have to run new wire.Is it hard to upgrade a circuit breaker to get more power available in a room?
Basicall, add up the total watts of his equiptmetn and divide by 120. So for example, to find out how many amps you are pullin: watts(1200) / volts (120)= amps (10).Hi brick and others,
My friend will be setting up a Flowering Room in a 8ftx8ftx8ft walk in closet with no outlets inside of it. There are numerous regular wall outlets in the room attached to the walk in closet. How do you suggest he hooks the following room up. I am not aware of how many amps each wall outlet is.. im assuming its just a standard wall outlet. How do you suggest he gets this up and and working in a safe manner? All help is appreciated. Thanks!
He will have 2x1000 hps with reflective air cooled hoods. These will be cooled by atleast a 300cfm inline fan.
He will have a canfan 100 with carbon scrubber which moves about 750cfm that will exhaust through a cut hole in the door of the walk in closet. One hole for the exhaust canfan100 and also one hole near the bottom for the inline fan.
Also he will have an oscillating fan in the room to move air around.
****My question however is that even though i know the lights will come with a complete system with a ballast for each light i was basically wondering how to plug all these different things in.
He doesnt want to overload the circuit or blow anything or worse start a fire.
***So will he be able to simply run an extension cord out of the room to a near by wall outlet and plug it in there, then connect the other end of the extension cord in the flower room to a multi power outlet or adapter(otherwise known as a power strip). would i be able to plug and successfully run everything in the room i have named by just simply plugging it into the powerstrip thats connected to the extension chord or will this not work?
Should the fans be connected together on one powerstrip and extension chord and run into the other room outside the walk in closet where they can be plugged in? and then do the same for the lights on another powerstrip and extension chord?
I really have no idea what would work best. Please let me know anything you suggest. He feels this room has great potential, he just wants to make sure he does it the right way.
If anyone could answer my questions I would really appreciate it.
Holy shit, now that's what I call dedication! With that kind of electricity drain though, the solar panels are/were merely props. Same for the wind turbines. Most people have no idea how much energy a kwh really is. And I used to be in the solar business! Most of the people we dealt with were just trying to stop getting screwed over by the energy companies and get off the grid. Also, most of them were older, retired people with things like that to think about and spend their money on. Unfortunately, at least in Cali, without the huge rebates the state offers, photovoltaic systems would be far fewer. Energywise, most families could probably equal or even surpass their electricity demands more by using gas ranges and dryers or even by (and I hate to admit it) hang drying their laundry.I helped a friend set up a 10000 watt (10 1000w) system. We did it over 6 months to lull suspicions. Suddenly jumping to 10000 watts is very suspicious, but gradually getting up that high over x number of months isn't as bad. We also had another 100A service box installed under the auspices of using it for pool and hot tub heating. I believe he eventually added some solar panels and wind turbines to help offset his power usage.
thanks for your help brick.. i honestly have no experience at all with anything electrical. how would i run new dedicated lines to the room? The walk in closet is attached to a master bath room with plenty of outlets and the master bedroom is also right next to the closet. could i run two separate lines or thick heavy duty extension chords, One to the bathroom outlets and one to the master bedroom outlet from two separate powerstrips in the closet?Installing a circuit breaker is a matter of turning a flat head screw driver a couple times. But you can't put a larger circuit breaker into replace a smaller one becuase the wire size is only suited for that breaker size. If you want to upgrade your breaker size you will have to run new wire.
Basicall, add up the total watts of his equiptmetn and divide by 120. So for example, to find out how many amps you are pullin: watts(1200) / volts (120)= amps (10).
Usually, 1 room will have 1 dedicated circuit. But, I think that you are going to pull well over 15 amps, which is what a normal house circuit is. I would suggest after finding out how many amps you are pulling, to run new dedicated lines to this room. That way you have no fear of tripping breakers and not have other rooms go out.