any problem with running a 40a 240v timer on a 240v 80a breaker?

bba

Well-Known Member
fried one of my 120v wall circuits so im running a 240v dedicated line for my 2 1000w nextgen ballasts.

~BBA
 

roka

Well-Known Member
That would be fine... as long as you are not exceeding the 40amp timer limits... AND the wiring for the 80amp circuit is appropriate size. What circuit in your place is on a 80amp circuit? Also, don't double-tap the 80amp breaker... good way to cause some problems for yourself.
 

bba

Well-Known Member
well its my furnace circuit, and the wire is huge!, dont know the guage off hand but im bettin its 6 or 4, the wire im using to the outlet will be a 10/3, and like i said running pretty much 9-10 amps off that circuit only.
 

roka

Well-Known Member
10/3 is adequate for 30amp. How are you making the connection to the existing circuit? Junction box? I hope. And really, you should put a 30amp fuse or circuit breaker disconnect in there to be proper and safe (after the furnace connection).
Let me know if your not following me. I will sketch you a diagram if you need it.
 

roka

Well-Known Member
Also... you mentioned you are only running 2 - 1000's. You really only need to use 12/3 with a 20amp two pole ciruit breaker or fused disconnect.
 
Top