Hey guys, I am running into some issues with my air conditioning. I have a 3ton A/C for a 18x14 area using LED's there are about 2k total watts on the ceiling. I was initially going to use much more powerful lights, but have since got 320Watt fixtures, there are 6 of them.
I am using a Trolmaster to control the A/C. The temp is set to 86, when the AC kicks on it will cool the room down to like 79-81 degrees. It then takes the lights way too long to get the room temp back up. In the morning, when lights turn on. It takes almost 2 hours to get up to 86.
I 'think' my options are to replace the blower for the furnace with something less powerful or find a thermostat that will turn off the A/C faster. I really dont like these temp swings and would replace the Trolmaster if needed.
What do you think i should do?