    240V lighting deficiency

    hey thanks for all the help. turns out the breaker was in the box wrong. the previous owner had the breaker on only one side, instead of straddling the bars. All is well now thanks again.
  2. D

    240V lighting deficiency

    seems i should be getting a 240 reading when i test my black and white wires coming off the breaker,No? but i get nothing. So maybe this is a bad breaker?
  3. D

    240V lighting deficiency

    the light works at 120v on a different circuit, can i safely wire the light 240, straight to the breaker.
  4. D

    240V lighting deficiency

    when i test to ground and each line it reads 120v, the same for the load side with the timer on. should i be getting a 240 reading? if so, how?
  5. D

    240V lighting deficiency

    This is the Intermatic T103 Timer Do I have this all wrong, any idea? thanks
  6. D

    240V lighting deficiency

    well i installed this same setup maybe 10 years ago and i thought i remembered how to. ive ran 10/2 wire from a double pole 30 amp breaker into my t103 timer. the 2 incoming hots(white and black) go to the line side or terminals 1 and 3. The outgoing white and black, to my 1000 watt ballast...