kpw555
Well-Known Member
I have posted this question in another thread also, as I am ready to go get what I need to finish this project today.
I am installing a mini split AC unit and there is a connection between the inside unit and the outside unit. I'm kind of stuck on the wiring for the inside units. The inside units operate on 30vdc supplied from the outside unit where the mains connect. There are also two additional control wires that must come from outside to inside for a total of 4 wires, all low voltage.
According to the manual that came with the inside units, each requires 1.8 full load amps to operate.
While the schematic calls for 14ga(seems a bit of overkill)wire for this connection, as the units are less than 15' from the source, and the fact that 16ga wire is rated to carry 3.7 amps for power distribution, and the fact that I can get a 25' roll(plenty to wire both units) of stranded 16ga 4 conductor trailer wire for $15 at Autozone...........................................I should be fine with that, so long as connections are solid, right?. Thanks for any advice.
I am installing a mini split AC unit and there is a connection between the inside unit and the outside unit. I'm kind of stuck on the wiring for the inside units. The inside units operate on 30vdc supplied from the outside unit where the mains connect. There are also two additional control wires that must come from outside to inside for a total of 4 wires, all low voltage.
According to the manual that came with the inside units, each requires 1.8 full load amps to operate.
While the schematic calls for 14ga(seems a bit of overkill)wire for this connection, as the units are less than 15' from the source, and the fact that 16ga wire is rated to carry 3.7 amps for power distribution, and the fact that I can get a 25' roll(plenty to wire both units) of stranded 16ga 4 conductor trailer wire for $15 at Autozone...........................................I should be fine with that, so long as connections are solid, right?. Thanks for any advice.