new setup

highwayman

Well-Known Member
would i beable to run a 600watt hps and fans in the one power bar on a outdoor digital timer? the extension chord comes from an outlet outside my house would it be enough power? and there will be one 12" fan 3 cpu fans hooked up to a adapter 1 squirl cage fan for exhaust and another fan for an inlet for air... will this be enough ventilation in the room for 6 plants and to keep temps down? the room is 3'x2'x9' (width x depth x height)
 

desertrat

Well-Known Member
would i beable to run a 600watt hps and fans in the one power bar on a outdoor digital timer? the extension chord comes from an outlet outside my house would it be enough power? and there will be one 12" fan 3 cpu fans hooked up to a adapter 1 squirl cage fan for exhaust and another fan for an inlet for air... will this be enough ventilation in the room for 6 plants and to keep temps down? the room is 3'x2'x9' (width x depth x height)
you need to know what else is on that circuit and what amperage its rated for. total up the wattage of every device, divide by 110 and check against the circuit breaker/fuse rating of the circuit; the total amperage should be less than 80% of the rated amperage. OR - just hook everything up and see if the breaker trips.

your fan question can really only be answered by trial and error.
 
Top